I connected a generator to an 8kw Deye system, but the inverter does not seem to accept it?

1) Grid And Gen Both can’t work at the same time.
2) Gen Dry contact should connect to 3.6/5kw to GV/5&6 and 8Kw to GS/7&8.
3)Gen Signal and Gen Charge should Be Clicked.
4)Gen Load ON Batt should be more than Battery % or Voltage.
5) If using Time of use – SOC should be more than Gen ON (At this SOC, Gen will stop).
6) If not using Time of use – Default is set to 95%, Gen will be Off when the battery reaches 95%.